Commercial Top Performer Sizing Guide


NOTE – All of the following Top Performer sizing is based on dedicated boiler input of 137,000 BTU's per tank, using constant 180 degree F. boiler water, with an 6 gpm minimum flow rate.

IMPORTANT – None of the sizing examples below take under consideration "whirlpool" type tubs. If these are present, they must be considered separately.

APARTMENTS

For one and two bath, high rise and garden types to include showers, lavatories, kitchen sinks, dishwashers, and clothes washers. Clothes washers can either be in individual apartments or centrally located.

 

 

Application

Requirements

    Up to 12 apartments

    1 - S70-D-TP

    13 to 28 apartments

    2 - S70-D-TP

    29 to 48 apartment

    3 - S70-D-TP

    49 to 72 apartments

    4 - S70-D-TP


NURSING HOMES

Based on tubs and showers, wash basins, slop sinks, kitchen equipment w/food service for patients and general cleaning purposes in building. Does not include laundry and hydro-therapy equipment.

 

 

Application

Requirements

    Up to 27 beds

    1 - S70-D-TP

    28 to 60 beds

    2 - S70-D-TP

    61 to 98 beds

    3 - S70-D-TP

    99 to 148 beds

    4 - S70-D-TP


MOTELS

To include tubs/showers, lavatories and general cleaning. Food service and laundry not included.

 

 

Application

Requirements

    Up to 20 rooms

    1 - S70-D-TP

    21 to 46 rooms

    2 - S70-D-TP

    47 to 79 rooms

    3 - S70-D-TP

    80 to 116 rooms

    4 - S70-D-TP

    117 to 170 rooms

    5 - S70-D-TP


FEMALE COLLEGE DORMITORIES

Includes showers, lavatories, slop sinks, and washing machines. Does not include hot water use for food service.

 

 

Application

Requirements

    Up to 26 students

    1 - S70-D-TP

    27 to 60 students

    2 - S70-D-TP

    61 to 102 students

    3 - S70-D-TP

    103 to 148 students

    4 - S70-D-TP


MALE COLLEGE DORMITORIES

Includes showers, lavatories, slop sinks, and washing machines. Does not include hot water use for food service.

 

 

Application

Requirements

    Up to 31 students

    1 - S70-D-TP

    32 to 70 students

    2 - S70-D-TP

    71 to 116 students

    3 - S70-D-TP

    117 to 180 students

    4 - S70-D-TP


HIGH SCHOOLS

Daytime use for Senior High Schools grades 9 or 10 through 12 for showers, lavatories, dishwashing machines, kitchens, and general cleaning purposes. Daytime use for Junior High Schools grades 7 through 8 or 9 would be the same as for Senior High, except when no showers are included. In that case, Junior High Schools would follow recommendations made for Elementary schools.

 

 

Appplication

Requirements

    Up to 160 students

    1 - S70-D-TP

    161 to 374 students

    2 - S70-D-TP

    375 to 613 students

    3 - S70-D-TP

    614 to 865 students

    4 - S70-D-TP


ELEMENTARY SCHOOLS

Hot water for lavatories, cafeteria, kitchen and general cleaning purposes. Does not include showers. Also use this table for Junior High Schools with no shower facilities.

 

 

Application

Requirements

    Up to 280 students

    1 - S70-D-TP

    281 to 565 students

    2 - S70-D-TP